U1000 AR02V 3x240+95

Description

Description

Standards

  • Product
    IEC 60502; XP C 32-321

Application

U-1000 AR2V cables can be used in all low voltage power installations. Multiconductors cables are adapted to remote control and telecontrol installations.

In case of high ambiant temperature, use correction coefficient.

Installation

These cables can be fixed on cable trays, within conduits or fixed to walls. They also can be buried directly with extra mechanical protection.

Cross sections 1,5 - 2,5 and 4 mm² have to be of class 2 flexiblility, if the cable is connected to equipment subject to vibration.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor material
Aluminum
Insulation
XLPE (chemical)
Outer sheath
PVC
Sheath colour
Black
Conductor shape
Circular
With smaller neutral conductor
Yes

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
240 mm²
Number of cores
4
Approximate weight
3806 kg/km
Ground conductor cross-section
95 mm²
Maximum outer diameter
52.5 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Permissible current rating in open air
412 A
Permissible current rating when buried
393 A
Voltage drop, single phase
0.29 V/A.km

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good
Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Max. conductor temperature in service
85 °C
Short-circuit max. conductor temperature
250 °C
Length
500 m
Operating temperature, range
-10 ... 60 °C
Packaging
Drum
Flame retardant
C2, NF C 32-070
Weather resistance
Very good
Chemical resistance
Accidental
Bending factor when laying
6 (xD)

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close